Project Overview
This company is located in Indonesia and is the installation telecommunication service company in Indonesia. Mainly used DC multi-function meter PZ72L-DE/C and shunt, used to measure and monitor current and voltage in telecommunication station.
PZ Series DC Programmable Intelligent Electric Meters
PZ series intelligent DC energy meter is designed for applications such as DC panels, solar power,telecommunications base stations, and charging posts.
This series of instruments can measure voltage, current, power,forward and reverse power in DC system. It can be used for local display, and connected with industrial control
equipment, computers, form a measurement and control system.
And it has a variety of external excuse functions for the user to choose: RS485 communication interface, Modbus-RTU protocol, relay alarm output, digital input/output. According to different requirements, through the instrument panel keys, you can set the ratio, communication parameters.
The product meets the relevant technical requirements of the standard Q/GDW1825-2013 DC power meter specification,GB/T29318-2012 Non-vehicle charging electric energy metering for electric vehicles,Q/GDW364-2009 Single-phase energy meter
specification.
Technical Parameter
Parameter | Description&Value | |
Input
|
Rated Voltage | DC Voltage Input: 0~1000V DC (via direct connetion); Input Resistance: ≥ 6kΩ/V |
Rated Current | DC Current Input: 10A DC (via direct Connection); 0~20mA or 4~20mA (via Hall Sensors); 75mV (via Shunts) | |
Overload |
Current&Voltage input overload:1.2 times rated value(continuous); 10 times rated value /1 second |
|
Power Consumption |
Power consumption of each current input circuit is less than 1mW |
|
Measuring Accuracy
|
Class | 0.5% |
Power Supply
|
Voltage Range | 85-265V AC/DC; 20~60V DC (±20%) |
Power Consumption |
≤ 2W |
|
Pulse Constant |
Voltage and current specifications:750V、300A,Default pulse constant:100imp/kWh
|
|
Voltage and current specifications:1000V、300A,Default pulse constant:100imp/kWh
|
||
Insulation resistance |
≥ 100MΩ |
|
Power frequency withstand voltage |
Between Power supply//Switching Output// Current Input//voltage Input and Transmitting// Communication //Pulse Output//switching input AC 2 kV 1min; Between Power supply、switching output、Current Input、voltage Input AC 2 kV 1min; Between Transmitting、Communication、Pulse Output、switching input AC 1kV 1 min; |
Product Function
Function | Description&Value |
Measurement
|
1-circuits DC Voltage, Current, Power, kWh |
Display
|
LCD display |
Communication
(Optional)
|
RS485,Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity) Baud Rate 1200~38400 bps etc. |
DI/DO Switching
(Optional)
|
DI (Digital input): 2-channel digital input,dry contact, built-in power supply DO (Digital output): 2-channel digital output (relay output) with NO Contact, Capacity: 2A/30V DC or 2A/250V AC |
±12V Power Output
(Optional)
|
Serve as the power supply for 1 Hall Sensors with ±12V DC |
Multi-rate/tariff
(Optional)
|
2 Time Schedules; 4 Time Zone for a year; 12 time periods by days set for 1 time schedule; 4 Tariff Rates (Spike, Peak, Flat, Valley); Min. Time Interval=15 min. |
5. Installation Picture